Elpress Catalogue

8:4 Filler piece To splice the copper screen around the conductors, a filler piece is required that is placed between the screw and the screen. To select the correct filler piece, see table. Requires 2 filler pieces per splice. SC95N PEN Name Screen conductor Note SC95N/PEN 16-57* *16-50 mm² (SC95N) / 16-57 mm² (SC95R95S) SC150N/PEN 21-95 SC240/PEN 29-146 Shearbolt terminals 10 - 630 mm² (pre-assembled screw) Properties: • screw material: brass for minimum friction • pre-assembled shear-off screws for easy handling • voltage range: 1 kV for SL50N-10-12, SL95N-10-12 and SL240N-10-12, 1-36 kV for the others • meets the requirements of standard IEC 61238-1 • the terminals are of the bimetallic type Cable type round mm² Cable type sector mm² Name Screen conductor Screen conductor (with filling piece) Screw W mm d D N cc a L L1 t s 10-50 10-50 SL50N-10-12 10-35 M10, M12 25,5 12 20/17,3 12,5 13 87 44 5,9 32 35-95 35-95 SL95N-10-12 57-95 16-50 (SC95N/PEN) M12, M10 27,3 16 17/23 12,5 13 96 52,5 4,7 56 120-240 120-240 SL240N-10-12 29-146 (SC240/PEN) M12, M10 31,5 25 38/33,1 15 13 144,586 7,6 76 185-240 SL240R-12-16 M12, M16 30 20 33,5 15 12 134 79 7,9 75 185-240 SL240R-12X2-40 M12x2 31,5 20,0 33,5 15 40 12 174 79 7,9 75 300-400 SL400R-12X2-40 M12x2 42 25,8 41,5 15 40 12 210 103 9,6 99 630 SL630B-12X2-40 M12x2 55 33,0 49,0 17 40 12 218 115 11,7 108 t = palm thickness, s = strip length